HomeProductsThree Phase UPSGT33 Rack Online UPS Power Supply 10/15/20/30/40kVA
  • 10-40kVA Rack-Mounted high frequency uninterruptible power supply-Gottogpower
  • 10-40kVA Rack-Mounted high frequency uninterruptible power supply-Gottogpower
  • Rack Uninterruptible Power Supply10~40kVA

GT33 Rack Online UPS Power Supply 10/15/20/30/40kVA

🔺10kVA/15kVA/20kVA/30kVA/40kVA Rack Mounted Uninterruptible Power Supply(ups).
🔺3P/3P,3P/1P,1P/1P, Online double conversion.
🔺Application for Government, Finance, IT, Education, Transportation, Broadcasting, Medical, Energy, etc.

Mounted in 19 inch rack, or install as tower UPS.

7 inch touch LCD with IoT functions.

Flexible configuration as 3/3,3/1,1/1.

High power density, small volume, 30kW in 3U.

High reliability and environment adaptibility.

Inquire Now
  • 10-40kVA Rack-Mounted high frequency uninterruptible power supply-Gottogpower
  • 10-40kVA Rack-Mounted high frequency uninterruptible power supply-Gottogpower
  • Rack Uninterruptible Power Supply10~40kVA

Share:

  • Introduction

  • Parameters

  • Download

  • Core Performance Advantages
  1. Super Power Adaptability

–Low Harmonic Interference: Input THDi <3% (100% linear load);

–High Power Factor: >0.99.

  1. Pure and stable output
  • High-precision voltage stabilization: voltage precision: ±1.0.
  1. Frequency Accuracy: ±0.1%
  • Pure Sine Wave: Linear Load THDu: <1%; Non-linear Load THDu: <5%;
  • Extremely Fast Dynamic Response.
  1. Strong overload capability
  • 110% load: 1 hour duration; 125% load: 10 minutes duration; 150% load: 1 minute duration.
GT33 Rack Online UPS Power Supply 10/15/20/30/40kVA

    5. Intelligent Battery Management

    • Precise Charging Control: Charging Voltage Accuracy: ±1%
    • High Voltage DC System: 240VDC

    6. Interaction and Expansion

    GT33 Rack Online UPS Power Supply 10/15/20/30/40kVA

    • Standard communication interfaces: USB, RS232, RS485, dry contact

    • Optional expansion modules: SNMP card, AS400 card, Parallel kit, LBS, Air filter, Cold start

    Model GT33010RL GT33015RL GT33020RL GT33030RL GT33040RL
    Rate Power 10kVA 15kVA 20kVA 30kVA 40kVA
    Main
    input
    Input 3P5W (3P+N+PE)
    Rate Voltage 380/400/415VAC(L-L) 220/230/240VAC(L-N)
    Rate Freq. 50/60Hz
    Input PF >0.99
    Current distortion THDi<3%(100% Linear load)
    Voltage range 304 478VAC(L-L)full load 304 228VAC (L-L) power derate from 100% to 75%
    Freq. range 40-70Hz
    Battery Rate voltage ±240VDC
    Charging capacity 20%*Pout
    Charging accuracy ±1%
    Bypass Rate voltage 200/208/220VAC(L-L)
    Voltage range Range: -40%- +25% , Settable, default -20% +15%
    Overload 110%, long time operation110%< load<125%, 5 mins
    125%<load<150%,1 min
    >150%,1 second
    Inverter Rate voltage 380/400/415VAC(L-L) 220/230/240VAC(L-N)
    Rate Freq. 50/60Hz
    Output PF 1
    Voltage accuracy ±1.0%
    Load response <5% (20% - 80% -20% step load)
    Recovery time < 20ms (0% - 100% -0% step load)
    Output THDu <1%(linear load),<5% (non-linear load according to IEC 62040-3)
    Overload 110%,1 hour 125%,10 mins 150%,1 min >150%,200ms
    Frequency accuracy 0.001
    Synchronize window Settable ±0.5Hz-±5Hz default ±3Hz
    Slew rate Settable 0.5Hz/S-3Hz/S default 0.5Hz/S
    Crest factor 3:1
    Phase Accuracy 120°±0.5
    System Efficiency Normal Mode96%;Battery mode96%
    Display LED + 7 inch touch LCD
    Certification- Safety IEC62040-1, IEC60950-1
    Certification- EMS IEC62040-2 IEC61000-4-2(ESD) IEC61000-4-3(RS) IEC61000-4-4 (EFT) IEC61000-4-5 (Surge)
    IP degree IP20
    Configuration USB, RS232, RS485, Dry contact
    Option SNMP card, AS400 card, Parallel kit, LBS, Air filter, Cold start
    Environment 0-40 (operation) -25 ~70 (storage) 0-95% (Humidity, non-condensing)
    Dimention (W*D*H)mm 440*774*130 (3U) 440*788*174 (4U)