HomeProductsSingle Phase UPSGT11Li Series 1~3kVA Online Rack UPS
  • GT11Li Series1~3kVA online Rack UPS
  • GT11Li Series1~3kVA online Rack UPS
  • GT11Li Series1~3kVA online Rack UPS

GT11Li Series 1~3kVA Online Rack UPS

🔺Power range: 1~3kVA.
🔺Operation: 1P/1P, online double conversion.
🔺Applications: Government, Finance, IT,Education, Transportation, Broadcasting, Medical, Energy, etc.

Inquire Now
  • GT11Li Series1~3kVA online Rack UPS
  • GT11Li Series1~3kVA online Rack UPS
  • GT11Li Series1~3kVA online Rack UPS

Share:

  • Introduction

  • Parameters

  • Download

● Online double conversion

Online double conversion delivers fully isolated, stable, pure, uninterrupted power to loads.
It ensures zero transfer time, complete utility isolation, and voltage/frequency stabilization,
providing supreme protection and operational reliability for critical sensitive equipment.

Schematic diagram of a double conversion UPS
GT11Li Series 1~3kVA Online Rack UPS

Output PF=1, high load adaptability.

Output PF=1 maximizes power utilization capacity, minimizes line losses and heat generation, and reduces electricity costs.

High efficiency up to 95.5%.

High efficiency up to 95.5% dramatically reduces energy waste, minimizes heat generation and cooling requirements, thereby cutting electricity costs. It also lowers operating temperatures to extend critical component lifespan and enhance system reliability.

GT11Li Series 1~3kVA Online Rack UPS
Voltage-Range-Indication-Chart

● Wide input voltage range of 110~300Vac.

Wide input voltage range significantly reduces battery transfers by maintaining rectified power during line fluctuations, thereby extending battery life and ensuring continuous critical load operation

Model GT1101BRLi GT1101LRLi GT1102BRLi GT1102LRLi GT1103BRLi GT1103LRLi
Rate Power 1kVA/1kW   1kVA/1kW   2kVA/2kW 2kVA/2kW 3kVA/3kW   3kVA/3kW
Cold start Default output 50/60Hz
Input voltage range 110~300VAC;100% load@176VAC~276VAC,100%~50% power derating@110VAC~176VAC,50% load@276VAC~300VAC
Input power factor ≥0.99
Frequency range 50/60±5Hz(default),±3Hz/±10Hz(settable)
Output power factor 1.0 
Output Rate voltage 208VAC/220VAC/230VAC/240VAC
Load response ≤5%(0%-100%-0%step load)
Recovery time ≤40ms (0%-100%-0%step load)
Output THDu ≤2%,Linear load;≤5%non-linear load according to IEC62040-3
Transfertime Main to BAT
INV to BYP 4ms
Efficiency (normal mode) 95% 95.50%
Noise (1 meter) 45dB@>70%load or >6A charge 50dB@>70%load or>6A charge 50dB@>70%load or >6A charge
Overload Normal 102%~110%:30mins,110%~125%:10mins,125%~150%:30 seconds
Battery mode 102%~110%:1min,110%~125%:10 seconds,125%~150%:5 seconds
Bypass mode <130%:long time,130%~150%:10mins,150%~180%:5 seconds
Battery Model 12.8VDC/9Ah 50Ah/100Ah 12.8VDC/9Ah 50Ah/100Ah 12.8VDC/9Ah 50Ah/100Ah
Quantity 2/3 Depend on external battery 4/6 Depend on external battery 6 Depend on external battery
Max charging 1-4A(settable) 1-12A(settable) 1-4A(settable) 1-12A(settable) 1-4A(settable) 1-12A(settable)
Rate voltage 25.6VDC/38.4VDC 51.2VDC/76.8VDC 76.8VDC/102.4VDC
Standard EPO,RS232
Option SNMP card,AS400,USB,RS485,BMS by dry contact,Air filter
Dimension ,W*D*H(mm) 440*440*86 440*580*86 440*580*86
Weight (kg) 15.5/16.8  9.5  20.7/23.3 9.7  23.8    10

Consulting Products