Application Fields:
- Suitable for small to medium-sized commercial and industrial energy storage applications.
- Utilizes time-of-use pricing to optimize charging and discharging times.
- Helps reduce electricity costs.

Modular UPS

Three Phase UPS

Single Phase UPS

Precision Air Conditioning

Data Center Service

Battery/Isolation Transformer cabinet

Network/Power Accessories

🔺 Voltage/Current Regulation Accuracy: ≤ ±1%
🔺 Cooling Method: Air Cooling
🔺 Protection Level: IP20
🔺 Ambient Temperature: -20~60°C
Flexible configuration with wide DC voltage range.
Compatible with air/liquid-cooled battery systems and various installations.
Intelligent peak shaving, supporting constant power, current, and voltage control.
Modular design, easy installation and maintenance.
99% conversion efficiency and high system availability.
Inquire Now
Introduction
Parameters
Download
Application Fields:
| Model | GT-CS125R |
| AC Parameters | |
| Rated AC Power | 125 kVA |
| Wiring Method | Three-Phase Four-Wire |
| AC Overload Capability | 137.5 kVA |
| Allowable Grid Voltage | 380/400(-15% to +15%) Vac |
| Allowable Grid Frequency | 50/60(-2.5% to +2.5%)HZ |
| Total Current Harmonic Distortion Rate | ≤ 3% |
| Power Factor | 0.99/-1-1 |
| DC Parameters | |
| Maximum DC Power | 137.5 kW |
| DC Voltage Range | 600-1000(650-1000 at full load)VDC |
| Maximum DC Current | 212 A |
| Voltage Regulation Accuracy | ≤ ±1% |
| Current Regulation Accuracy | ≤ ±1% |
| System Parameters | |
| Maximum Conversion Efficiency | 99% |
| Dimensions (W*H*D) | 520*220*680 mm |
| Weight | 75 kg |
| Noise | < 80 dB |
| Protection Level | IP20 |
| Allowable Ambient Temperature | -20 to 60°C (derating above 50°C) |
| Cooling Method | Air Cooling |
| Allowable Relative Humidity | 0-95%(no condensation) |
| Allowable Altitude | 3000 m (derating above 3000 m) |
| Communication Parameters | |
| Communication Interface | RS485, Ethernet, CAN |
| Communication Protocol | Modbus TCP/RTU. CAN 2.0 |
| BMS Integration | Supported |
Related Products
Consulting Products