Model |
GT020/10-EP |
GT040/10-EP |
GT060/10-EP |
Rate Power |
20kVA/20kW |
40kVA/40kW |
60kVA/60kW |
Main
input |
Input |
3P5W (3P+N+PE) |
Rate voltage |
380/400/415VAC(L-L);220/230/240VAC(L-N) |
Rate Freq. |
50/60Hz |
Input PF |
>0.99 |
Current distortion |
THDi<3%(100% Linear load) |
Voltage range |
304-478VAC(L-L)full load; 304~228VAC(L-L) power derate from 100% to 50%. |
Freq.range |
40-70Hz |
DC Voltage |
220VDC(compatible with DC busbars, also supports exlemal batlery packs) |
Bypass |
Rate voltage |
380/400/415VAC(L-L);220/230/240VAC(L-N) |
Voltage range |
Settable, Default -20%~+15%,Upper Limits:+10%,+15%,+20%,+25%:Lower Limits:-10%,-15%,-20%,-30%,-40%. |
Overload |
110%,long time operation; 110%<load<125%,10 mins;
125%<load<150%,1 min |
Inverter |
Rate voltage |
380/400/415VAC(L-L);220/230/240VAC(L-N) |
Rate Freg. |
50/60Hz |
Output PF |
1 |
Voltage accuracy |
±1.0% |
Output THDu |
<1%(linear load),<5% (non-linear load) |
Overload |
100-110% load:bypass after 1h; 110-125% load: bypass after 10min;125-150% load: bypass after 1min;150% load: bypass after 200ms |
Freguency accuracy |
0.1% |
Tracking range |
Settable,±0.5Hz-±5Hz,default ±3Hz |
Tracking rale |
Settable,0.5Hz/S-3Hz/S, default 0.5Hz/S |
Three-phase phaseaccuracy |
120°+0.5° |
System |
Efficiency |
96.5% |
Display |
LCD + LED + Color Touchscreen 7-inch |
Certifcation-Safety |
IEC62040-1,IEC60950-1 |
Certification-EMS |
IEC62040-2;IEC61000-4-2(ESD);IEC61000-4-3(RS);EC61000-4-4(EFT);IEC61000-4-5(Surge) |
IP degree |
IP20 |
Configuration |
USB, RS232, RS485, Dry contact, Air filter |
Option |
SNMP card, AS400 card, Parallel kit, APP/WiFi/Bluetooth |
Environment |
0-40℃(operation);-25℃-70℃(storage);0-95%(Humidity, non-condensing) |
Noise(dB)(1 meter) |
65dB @ 100% load, 62dB @ 45% load |
Dimensions
W*D*H (mm) |
Cabinet body |
442*710*307(7U) |
442 710*485(11U) |
442*661*906(20U) |
Cabinet |
442*751*397 |
442*751*575 |
442*841*976 |
Power module |
400*495*86(2U) |