| Modèle |
Rack-mounted Liquid-to-Liquid CDU |
| Puissance nominale |
CDU015RL |
CDU30RL |
| Performance Specifications |
| Heat Exchange Capacity (kW) |
15 |
30 |
| Dimensions (W*D*H)mm |
450*850*175(excluding handles and ports)
482*934*175(including handles and ports)
|
| Power Specifications |
220VAC, 50Hz/60Hz, Dual Power Supply Standard |
| Rated Power (kW) |
0.4 |
0.5 |
| Full Load Current (A) |
3.8 |
4.8 |
| Net Weight (kg) |
40 |
45 |
| Secondary Side System Parameters |
| Rated Supply LiquidTemperature (°C) |
40 |
| Rated Retur LiquidTemperature(°C) |
50 |
| Rated Circulation Flow (m³/h) |
1.4 |
2.8 |
| Available Headat Secondary Side |
≥10m |
| Adjustable Range for Secondary Side Supply Temperature |
25~45°C |
| Filter Precision |
100μm |
| Circulation Pump |
Variable Speed Pump, Standard 1+1 Redundant |
| Circulating Medium |
Deionized Water, Compatible with 25% Glycol Solution and Other Compatible Coolants |
| Refill System |
Built-in Automafic Refil System |
| Maximum Operating Pressure |
50 Bar |
| Pipe Connection Size & Type |
DN25, Quick-install Flange |
| Primary Side System Parameters |
| Rated Return Liquid Temperature (°C) |
35 |
| Rated Supply Liquid Temperature (°C) |
45 |
| Rated Circulation Flow(m³/h) |
1.4 |
2.8 |
| Allowed Inlet Liquid Temperature(Primary Side) |
10-35°C |
| Circulating Medium |
Deionized Water, Compatible with 30% Glycol Solution and Other CompatibleCoolants,Flexible Selection Based on Regional Conditions |
| Filter Requirement Precision |
≤270μm |
| Rated Pressure Drop Requirement(Primary Side) |
≤80 kPa |
| Maximum Operating Pressure |
10.0 Bar |
| Pipe Connection Size& Type |
DN25, Quick-install Flange |
| Modèle |
Rack-mounted Air-to-Liquid CDU |
| Puissance nominale |
CDU008RA |
CDU016RA |
| Performance Specifications |
| Heat Exchange Capacity (kW) |
8 |
16 |
| Dimensions (W*D*H)mm |
450*850*175(excuding handles and ports)
482*934*175(including handles and ports)
|
450*850*350(excuding handles and ports)
482*934*350(including handles and ports)
|
| Power Specifications |
220V/1N-50Hz/60Hz, Dual Power Supply Standard |
| Rated Power (kW) |
0.7 |
1.3 |
| Full Load Current (A) |
4.6 |
8.9 |
| Net Weight (kg) |
35 |
50 |
| Secondary Side System Parameters |
| Rated Supply Liquid Temperature(°C) |
40 |
| Rated Retumr Liquid Temperature(°C) |
50 |
| Raled Circulation Flow (m³/h) |
0.75 |
1.5 |
| Available Headat Secondary Side |
≥10m |
| Adjustable Range for Secondary Side Supply Temperature |
25-45°C |
| Fillter Precision |
100μm |
| Circulation Pump |
Variable Speed Pump, Standard 1+1 Redundant |
| Circulating Medium |
Deionized Water, Compatible with 25% Ethanol Solution and Other Compatible Coolants |
| Refill System |
Buil-in Automatic Refill System |
| Maximum Operating Pressure |
50 Bar |
| Pipe Connection Size & Type |
DN20, Quick-install Flange |
DN25, Quick-install Flange |
| Primary Side System Parameters |
| Rated Inlet AirTemperature (°C) |
25 |